e1973c-14
02.2004
50
Fire & Security Products
Siemens Building Technologies Group
Poll configuration data
Purpose
The polling of configuration data is only relevant for the service engineer, for controlling user
functions without the configuration tool.
Polling configuration data of detector zones
1.
Press
St
.
Display shows
2.
Select option 3.
4.
1.
Display shows
3.
Enter the desired zone number or
555
to select all zones and press
ok
.
Display shows
4.
Press
ok
to select only a single zone or
enter the number of the last zone of the
desired range and press
ok
.
Display shows
5.
Use and to scroll through the
configuration data of each selected
zone.
Display shows
6.
Use
hm
to go back to the submenu or
St
to terminate the configuration data polling.
Polling configuration data of address lines
1.
Press
St
.
Display shows
2.
Select option 3.
4.
2.
Display shows
3.
Enter the desired line number or
555
to
select all lines and press
ok
.
Display shows
4.
Press
ok
to select only a single line or
enter the number of the last line of the
desired range and press
ok
.
Display shows
5.
Use and to scroll through the
configuration data of each device of the
selected line.
Display shows
6.
Use
hm
to go back to the submenu or
St
to terminate the configuration data polling.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
Select ZONES: (range ### to ###)
Enter ZONE no.? (555 = all)
ZONE information for ### ZONES/ELEM:
↓
: forward
↑
: backwards
hm: back to menu Stop: end operating
ZONE ### selected. ok = single ZONE
Second ZONE No.? (range ### − ###)
Zn ###:###### tst:######dis:######## el
ele ## name=###### type=######
al=###### incr=###### dr=######
trouble=###### ln ## dev ##
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
Select LINES: (range ## to ##)
Enter line no.? (555 = all)
LINE information for ## LINES:
↓
: forward
↑
: backwards
hm: back to menu Stop: end operating
LINE ## selected. ok = single line
Second line no.? (range ## − ##)
line ###: ######, ### devices
device ### name=###### type=######
al=###### incr=###### dr=######
trouble=###### zn ### el ##
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...