Temporary isolation of a single detector
When has a single detector to be isolated?
Exceptional situations may occur, where it is preferable to isolate only single detector devices
instead of the whole detector zone. Such situations may be for example:
Construction work with smoke or heat development at a particular location within a large
zone with a lot of detectors
Malfunction of a detector in a zone with several detector devices
WARNING
A detector device that has been isolated cannot trigger any danger or fault messages! As
soon as conditions have returned to normal, isolated detector devices have immediately to
be switched on again!
i
If a single detector should be isolated the detector has to be identified clearly! If the detector
cannot be identified clearly, the whole detector zone should be isolated. A wrong isolation of
a detector can cause an unwelcome call of the fire brigade!
Single detector isolation procedure
1.
Press
St
.
Display shows
2.
Select option 2.
1.
2.
Display shows
3.
Enter the desired zone number.
Display shows
4.
Enter the desired element number.
Display shows
5.
Enter the desired disabling time in full
hours or
99
for permanent disabling.
Display shows
The yellow LED
isolation
is on.
6.
Press
hm
to finish the element disa-
bling procedure or enter a new zone
number to disable another single ele-
ment.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
DISABLE element:
> zone no.? (range ### − ###)
hm: back to menu Stop: end operating
zone ### SELECTED
> element no.? (range ## − ##)
hm: back to menu Stop: end operating
zone ### element ## SELECTED
> hours disabled? (99=permanent)
hm: back to menu Stop: end operating
zone ### elem. ## permanent DISABLED
> new element no.? (range ## − ##)
hm: back to menu Stop: end operating
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...