Detector test
Purpose and Principle
For function tests of the automatic fire detectors and the manual call points, zones of the fire
detection system are set into the “detector test mode”. In the detector test mode a responding
detector or manual call point triggers only a test alarm.
This allows individual on
−
site function tests, where automatic fire detectors deliberately are trig-
gered by means of special detector test equipement.
Manual call points are triggered either with a special test key or by opening the cover and actua-
ting the button.
Test alarm
A test alarm generates no danger message on the control console. Acoustic alarm devices, the
remote alarm transmission or any other control functions are not activated.
A test alarm is indicated on the text display of the control console as
test−ALARM ZONE #
.
It is
recorded in the event memory and automatically logged, if a printer is connected.
Frequency
Visual control of detectors and manual call points: Once a year.
Testing of all detectors and manual call points: Once every two years.
i
Differing national or local regulations always have priority!
Recommendations for function tests
Perform the function tests periodically. The frequency of function tests is determined by the
service engineer.
Switch only the fire detectors of a few zones at a time to detector test mode, never the entire
building.
For manual call points the function test needs to be performed only according to a sampling
plan, designed by the service engineer.
Test automatic fire detectors and manual call points separately. Never switch them to detec-
tor test mode simultaneously.
WARNING
A zone in detector test mode cannot trigger any danger or fault messages!
After completion of the test work immediatly set the fire detection system back to normal
operation!
Set only a few zones at a time to detector test mode, never all zones at the same time!
Setting single detector zones into detector test mode
1.
Press
St
.
Display shows
2.
Select option 4.
2.
3.
1.
Display shows
3.
Enter the desired zone numbers (e. g. 1
and 2; max. 4 zones). Use the
ok
key
to separate the numbers and the
del
key to cancel keying errors.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
No ’DET. TEST’ mode, set single zone(s):
> zone no.? (max. 4)
hm: back to menu Stop: end operating
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...