Test of Remote Transmission (RT)
Purpose and principle
In test mode the function of the remote transmission can be tested without activating an alarm
device or a manual call point.
The function of the remote transmission facility has to be checked periodically. The remote alarm
transmission and the remote fault transmission can be tested separately.
Frequency
The acoustic alarm devices have to be tested at least once a year.
i
Before the remote alarm transmission is tested, inform the fire brigade!
Test procedure for remote alarm transmission
1.
Inform the fire brigade
before a remote alarm transmission test will be performed.
2.
Press
St
.
Display shows
3.
Select option 4.
2.
1.
3.
To initiate the remote ALARM test.
Display shows
4.
If the fire brigade is informed, press
ok
.
Display shows
The test runs for 30 sec. The remaining
time is indicated.
After the test has finished, the submenu is displayed again.
If the remote alarm did not arrive at the fire departement, call the SIEMENS service organization
for repair.
"
The test can be stopped before expiration of the 30 seconds by pressing
hm
.
Test procedure for remote fault transmission
1.
Press
St
.
Display shows
2.
Select option 4.
2.
1.
4.
To initiate the remote FAULT test.
Display shows
The test runs for 30 sec. The remaining
time is indicated.
After the test has finished, the submenu is displayed again.
If the fault message did not arrive at the remote location, call the SIEMENS service organization
for repair.
"
The test can be stopped before expiration of the 30 seconds by pressing
hm
.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
ATTENTION: testing remote transm. ALARM!
>> fire brigade notified? > then: ok
hm: back to menu Stop: end operating
TESTING remote transm. ALARM (RT−alarm):
> remaining active time
hm: stop test Stop: end operating
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
TESTING remote transm. FAULT (RT−fault):
> remaining active time
hm: stop test Stop: end operating
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...