e1973c-11
02.2004
40
Fire & Security Products
Siemens Building Technologies Group
Test of acoustic alarm devices
Purpose and principle
The fire detection system is equipped with acoustic alarm devices distributed throughout the
building to alarm the fire brigade in case of fire. The function of the acoustic alarm devices has to
be checked periodically. The “horn test” activates all acoustic alarm devices for 30 seconds.
Frequency
The acoustic alarm devices have to be tested at least once a year.
Horn test procedure
1.
Press
St
.
Display shows
2.
Select option 4.
2.
1.
1.
To initiate the horn test.
Display shows
The horn test runs for 30 seconds.
The remaining time is indicated.
After the test has finished, the submenu is displayed again.
If an acoustic device did not respond in the test, call the SIEMENS service organization for repla-
cement or repair.
"
The horn test can be stopped before expiration of the 30 seconds by pressing
hm
.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
TESTING horn:
> remaining active time
hm: stop test Stop: end operating
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...