e1973c-6
02.2004
30
Fire & Security Products
Siemens Building Technologies Group
Alarm devices
When have alarm devices to be disabled?
Under normal conditions the alarm devices (e. g. horns or sirens) operate in active stand
−
by.
They are only disabled for:
Test of the fire detection system.
Maintenance and conversion works on the fire detection system.
WARNING
When the alarm devices are disabled, no acoustic alarm (except the buzzer) is issued in
case of fire!
i
Normally all acoustic devices are disabled together. Single devices or lines are only disa-
bled in exceptional cases. For the alarm devices there are always 2 lines, in some cases 4
lines, but max. 6 lines possible.
Disabling the alarm devices
1.
Press
St
.
Display shows
2.
Select option 2.
2.
1.
Display shows
3.
Enter the desired horn number or
555
for disabling all horns.
Display shows
for a few seconds
4.
Enter the number of a further device to
disable.
or
"
Press
St
to finish the procedure.
The desired alarm devices are disabled.
The yellow LEDs of the display fields
Isolation
and
Alarm horn fault/off
are on.
The text display indicates that no alarm message is pending.
Enabling alarm devices
1.
Press
St
.
Display shows
2.
Select option 1.
2.
1.
Display shows
3.
Enter the desired horn number or
555
to enable all horns.
Display shows
for a few seconds
4.
Enter the number of a further device to
disable.
or
"
Press
St
to finish the procedure.
The desired alarm devices are enabled.
The yellow LEDs of the display fields
Isolation
and
Alarm horn fault/off
are off, if no other
parts of the system are isolated.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
DISABLE horn:
> enter horn no.? (all=555)
hm: back to menu Stop: end operating
DISABLE horn:
> all horns DISABLED
timeout /hm: menu Stop: end operating
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
ENABLE horn outputs:
> enter horn no.? (all=555)
hm: back to menu Stop: end operating
ENABLE horn outputs:
> all horn outputs ENABLED
timeout /hm: menu Stop: end operating
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...