e1973c-8
02.2004
36
Fire & Security Products
Siemens Building Technologies Group
Functional testing of automatic AlgoRex-detectors
Required equipement
There are basically two kinds of automatic fire detectors: heat detectors and smoke detectors.
For
heat detectors
the detector tester RE6T is required, which simulates the temperatur rise with
a hot air blower.
Smoke detectors exist also as the variation multisensor smoke detector.
Both are tested with the
detector tester
RE6,
which also can be used as tool for the detector exchange. Smoke is detec-
ted by its light scattering, which is optically simulated by the detector tester RE6.
Identification of detectors
Smoke detectors, multisensor smoke detectors and heat detectors can be identified by their
housing, see illustration.
"
If the tested detector did not respond, exchange the detector unit.
Test procedure for detector tester RE6
1.
Set the desired zone into detector test mode (
page 34).
2.
Set the detector tester onto the detector and press for 1 second.
3.
Wait until the response indicator (red LED) located in the detector housing flashes.
4.
Possibly press again after 15
−
20 seconds for 1 second.
5.
Remove the detector tester.
The functional testing is completed.
"
If the tested detector did not respond, check the gas can inside the detector tester RE6 or the
battery inside the tester DZ1193. If defective detectors are found call the SIEMENS service
organization.
Test procedure for detector tester RE6T
1.
Set the desired zone into detector tes mode (
page 34).
2.
Set the detector tester onto the detector.
3.
Wait until the response indicator (red LED) located in the detector housing flashes.
4.
Remove the detector tester.
The functional testing is completed.
"
If the tested detector did not respond, exchange the detector unit.
Smoke detector
Detector tester RE6 (gas)
Multisensor smoke detector
Heat detector
Detector tester RE6T
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...