![Siemens Synova FC330A Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/siemens/synova-fc330a/synova-fc330a_operating-manual_379198028.webp)
e1973c-4
02.2004
24
Fire & Security Products
Siemens Building Technologies Group
Disable all zones
1.
Enter
555
to disable all zones in the
building.
Display shows
2.
Enter
99
for permanent disabling.
Display shows
or
"
Enter the desired disabling time in full
hours (e. g. 2).
Display shows
3.
Press
St
to finish the zone disabling
procedure.
Display shows
The yellow LED
isolation
is on.
Viewing disabled zones
Several zones disabled
Display shows
1.
Press key
F1
to open list.
Display shows
2.
Press key to view details.
Display shows
After last zone has been displayed, sy-
stem turns back to overview.
Display shows
Zone reactivation procedure
1.
Press
St
.
Display shows
2.
Select option 1.
1.
1.
Display shows
The yellow LED
isolation
is off.
zone ### − ### SELECTED
> hours DISABLED? (99=permanent)
hm: back to menu Stop: end operating
Permanent disabling
zone ### permanent DISABLED
(hm = end) new zone no.?
hm: back to menu Stop: end operating
Disabling for a few
hours
zone ### DISABLED for ## hours
(hm = end) new zone no.?
hm: back to menu Stop: end operating
parts of system DISABLED total:###
WED
21.7.00 15:00
parts of system DISABLED total:###
WED
21.7.00 15:00
display ISOLATIONS: total:###
(key:
↓
= forward /
↑
= backward)
F1: next section hm/Stop: end operating
display ISOLATIONS: total:###
zone ### − ### permanent DISABLED
↓
: forward F2:ext info
↑
: backwards
parts of system DISABLED total:###
WED
21.7.00 15:00
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
ENable zone: (range ### to ###)
> zone no.? (555 = all)
hm: back to menu Stop: end operating
Содержание Synova FC330A
Страница 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Страница 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Страница 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Страница 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Страница 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Страница 25: ...e1973c 4 02 2004 21 Fire Security Products Siemens Building Technologies Group Disable Enable System Parts ...
Страница 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Страница 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Страница 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Страница 47: ...e1973c 13 02 2004 43 Fire Security Products Siemens Building Technologies Group Other Functions ...
Страница 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...