70/88
Siemens Synco
900
CE1C2707en
Building Technologies
Function settings
05.07.2007
Switching differential 2-position
For rooms using 2-position actuators, the room controller’s switching
differential (0..20 K) can be set for every room. For your guidance,
refer to the standard settings:
Room type
Guide value switching differential
Radiator heating slow
0.8 K
Radiator heating fast
0.8 K
Floor heating slow
0.8 K
Floor heating fast
0.8 K
Main menu > Heating > Room X > Room controller >
Switching diff 2-pos:
Room
number
1 2 3 4 5 6
Room
name
Factory setting
0.8 K
0.8 K
0.8 K
0.8 K
0.8 K
0.8 K
Setting
SD
Room
number
7 8 9 10 11
12
Room
name
Factory setting
0.8 K
0.8 K
0.8 K
0.8 K
0.8 K
0.8 K
Setting
SD
Actuator running time
This defines the running time of the actuator used. This is the time
the actuator requires to travel from one end position to the other.
The setting only acts on 3-position actuators. It has no impact
on 2-position actuators and SSA955 radiator control actuators.
The actuator running time (1..600 s) can be set separately for every
zone valve. For your guidance, refer to the standard settings:
Room type
Guide value switching differential
Radiator heating slow
150 s
Radiator heating fast
150 s
Floor heating slow
150 s
Floor heating fast
150 s
Main menu > Heating > Room X > Room controller >
Actuator run time:
Room
number
1 2 3 4 5 6
Room
name
Factory setting 150 s
150 s
150 s
150 s
150 s
150 s
Setting
ALZ
Room
number
7 8 9 10 11
12
Room
name
Factory setting 150 s
150 s
150 s
150 s
150 s
150 s
Setting
ALZ
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......