Function settings
05.07.2007
Derivative action time Tv
The room controller’s derivative action time can be set for every
room. For your guidance, refer to the standard settings:
Room type
Guide value Tv
Radiator heating slow
450 s
Radiator heating fast
540 s
Floor heating slow
540 s
Floor heating fast
540 s
Main menu > Heating > Room X > Room controller >
Der action time Tv:
Room
number
1 2 3 4 5 6
Room
name
Factory setting 450 s
450 s
450 s
450 s
450 s
450 s
Setting
Tv
Room
number
7 8 9 10 11
12
Room
name
Factory setting 450 s
450 s
450 s
450 s
450 s
450 s
Setting
Tv
Neutral zone
For rooms using 3-position actuators, the room controller’s neutral
zone (0..20 K) can be set for every room. For your guidance, refer to
the standard settings:
Room type
Guide value neutral zone
Radiator heating slow
0.1 K
Radiator heating fast
0.1 K
Floor heating slow
0.1 K
Floor heating fast
0.1 K
Main menu > Heating > Room X > Room controller > Neutral zone:
Room
number
1 2 3 4 5 6
Room
name
Factory setting
0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
Setting
Neut.
Room
number
7 8 9 10 11
12
Room
name
Factory setting 0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
0.1 K
Setting
Neut.
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......