Commissioning the system
05.07.2007
Remove devices from the device list
If you want to remove a device, select – whenever possible – function
”Disconnect device“ (refer to page 58).
Sometimes, defective devices cannot be disconnected anymore. In
that case, you can remove the faulty device from the device list of the
central apartment unit as follows:
Main menu > Commissioning > Device list > Device X >
Delete device:
Use function “Delete device“ only if you are unable to remove
the device with function ”Disconnect device“.
Bus communication
Device address KNX TP1
You need to enter an unambiguous device address for the central
apartment unit. After entry, the central apartment unit checks whether
the address entered has already been assigned. If the address is still
free, the display returns to the “Basic settings“ menu. The value has
been adopted. Otherwise, you is prompted to enter a new address.
Main menu > Commissioning > Bus communication >
Basic settings > Device address:
Factory setting
255
Your setting
When using device address 255 (supply state), no data is
transmitted via bus. Use some other device address.
Bus power supply
State whether the Konnex bus is powered by an external power pack
(bus power supply “Off“) or whether the bus receives its power from
the central apartment unit (bus power supply ”On”).
Main menu > Commissioning > Bus communication >
Basic settings > Bus power supply:
Factory setting
On
Your setting
On
Off
•
Caution: Bus power supply by the central apartment unit
may only be switched on if only
one
OZW771 central
communication unit is connected to the Konnex terminal
of the central apartment unit
•
If several or other devices are connected to the bus, bus
power supply by the central apartment unit must be
switched off
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......