44/88
Siemens Synco
900
CE1C2707en
Building Technologies
Commissioning the system
05.07.2007
The smoke detector is connected by pressing the button on the front
of the detector for at least 2 seconds and then pressing the binding
button at the rear for at least 1 second. Then, the LED at the rear
blinks several times.
To confirm the successful connection, the central apartment unit
delivers a beep. Close the binding process by pressing the
Menu/ok
button.
Smoke detectors must be equipped with the smoke detector
module wave UNI M 255. For detailed information, refer to the
documentation covering the GAMMA wave products.
Connect DHW components
The following DHW plant components are assigned appropriate
inputs or outputs:
•
DHW sensor
•
DHW pump / valve
•
Electric immersion heater
On the DHW plant components, the respective input and
output functions must be set to “Via RF“, enabling an input or
output of a heating circuit controller to be assigned to them.
Connect the input for the DHW sensor
Inform the central apartment unit that you want to use a universal
input B of a heating circuit controller as a DHW sensor input:
Main menu > Commissioning > RF connections > DHW >
DHW sensor > Connect device:
Confirm subentry “Connect device“ by pressing the
Menu/ok
button.
To make the connection, you is prompted to press the binding button
on the device to be connected.
Select universal input B with the channel selection button (CH) on the
heating circuit controller. The LED of the selected channel blinks. If
the selected channel is not yet connected, the connection LED
flashes.
Now, press the multifunction button on the heating circuit controller.
The LED lights up green. When it starts blinking, you can release the
binding button.
A successful connection is shown on the display of the central apart-
ment unit and be confirmed with a beep. Close the binding process
by pressing the
Menu/ok
button.
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......