20/88
Siemens Synco
900
CE1C2707en
Building Technologies
Commissioning the system
05.07.2007
Main menu > Commissioning > Basic configuration > DHW >
DHW sensor:
Factory setting
---
Your setting
---
Via RF
B (local)
DHW charging pump / diverting valve
State whether a DHW charging pump or DHW diverting valve is used
and how it is controlled.
Setting Description
---
Inactive – no DHW charging pump / diverting
valve installed
Via RF
DHW charging pump / diverting valve connected
to relay output Qx of an RRV91… heating cir-
cuit controller
Q1 (local)
DHW charging pump / diverting valve connected
to relay output Q1 of the central apartment unit
Main menu > Commissioning > Basic configuration > DHW >
DHW pump/valve:
Factory setting
---
Your setting
---
Via RF
Q1 (local)
Electric immersion heater
State whether an electric immersion heater is used and how it is
controlled.
Setting Description
---
Inactive – no electric heater installed
Via RF
Electric heater connected to relay output Qx of
an RRV91… heating circuit controller
Q1 (local)
Electric heater connected to relay output Q1 of
the central apartment unit
Main menu > Commissioning > Basic configuration > DHW >
El immersion heater:
Factory setting
---
Your setting
---
Via RF
Q1 (local)
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......