Communication
11.2 Communication via Modbus
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
153
11.2
Communication via Modbus
11.2.1
General information
The current process values and parameters can be exchanged via the RS485 interface with
Modbus RTU or the Ethernet interface with Modbus TCP/IP. It is possible to use both
interfaces for the communication.
Note
The SIWAREX WP231 is designed for use in secure (closed) networks and does not have
any protection against unauthorized data traffic.
The following chapters describe the specifications for handling communication. The following
functions can be executed:
●
Export parameters from the electronic weighing system
●
Write parameters
●
Export current process values
●
Monitor messages
11.2.1.1
Principle of data transmission
This description is valid for communication via Modbus RTU and Modbus TCP/IP.
The standardized MODBUS protocol is used for communication. The master function is
always in the connected communication partner, while the SIWAREX module is always the
slave.
Data transfer is bidirectional. The master function is always in the connected module which
“controls” the communication with corresponding requests to the respective SIWAREX
module address. The SIWAREX module is always the slave and responds to the requests of
the master, provided that the address matches, with a response frame.
Each Modbus partner has its own address. The SIWAREX module has the default address
1. This address can be changed as a parameter (e.g. in SIWATOOL). This address is
without significance if the Ethernet interface is used because the connection is based on the
IP address.
If the RS485 interface is used, the following character frame is valid:
Start bit
1
Number of data bits
8
Parity
Even
Stop bit
1
Содержание SIWAREX WP231
Страница 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Страница 24: ...Application planning 4 2 Parameter assignment options SIWAREX WP231 24 Manual 07 2014 A5E31238908A 02 ...
Страница 108: ...Scale parameters and functions 8 15 DR 15 tare settings SIWAREX WP231 108 Manual 07 2014 A5E31238908A 02 ...
Страница 131: ...Scale parameters and functions 8 26 DR 48 date and time 2 for Modbus SIWAREX WP231 Manual 07 2014 A5E31238908A 02 131 ...
Страница 132: ......
Страница 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Страница 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Страница 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...