Scale parameters and functions
8.19 DR 30 current process values
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
113
8.19
DR 30 current process values
8.19.1
Overview
Current states and process values in the scales can be monitored using process values and
advanced process values from data record DR 31. Monitoring selected data during
commissioning is extremely useful as it helps you to optimize parameters.
Procedure
●
Read data record DR 30 cyclically or on a time-triggered basis
●
Display/analyze the required tags
It is not always necessary to cyclically read data record DR 30. If the relevant process tags
are already selected in data record DR 14 (Page 106), they are immediately transferred via
the I/O interface. In this case, these tags and all status bits and messages are accessible
without data record communication.
Table 8- 20 Assignment of data record 30
Variable
Note
Type
Length
(bytes)
Rw
Default
Min.
Max.
Modbus
registers
Data record
number
Contains no. of data record
USHORT
2
r
30
-
-
3000
Length
Data record length infor-
mation
USHORT
2
r
60
-
-
3001
Application
Information about which
application the data record
belongs to
USHORT
2
r
101
-
-
3002
Version identi-
fier
Information about current
data record version
USHORT
2
r
1
1
255
3003
1/4d zero
Set if gross is less than ±
0.25e
BIT
2
r
0
-
-
3004.16
9e max
Set if the weight of the gross
weighing range is exceeded
by more than 9 display inter-
vals (d)
BIT
0
r
0
-
-
3004.15
Tared
Set if the tare memory is not
equal to zero
BIT
0
r
0
-
-
3004.14
Manual tare 1
set (pT)
Set if the tare memory is
assigned an external speci-
fied value 1
BIT
0
r
0
-
-
3004.13
Reserve
BIT
0
r
0
-
-
3004.12
Waiting for
standstill
Set if module is waiting for
standstill to execute com-
mand
BIT
0
r
0
-
-
3004.11
Standstill
Set if standstill condition is
met
BIT
0
r
0
-
-
3004.10
BIT
0
r
0
-
-
3004.9
Empty
Set if "Empty" condition is
met
BIT
0
r
0
-
-
3004.8
Содержание SIWAREX WP231
Страница 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Страница 24: ...Application planning 4 2 Parameter assignment options SIWAREX WP231 24 Manual 07 2014 A5E31238908A 02 ...
Страница 108: ...Scale parameters and functions 8 15 DR 15 tare settings SIWAREX WP231 108 Manual 07 2014 A5E31238908A 02 ...
Страница 131: ...Scale parameters and functions 8 26 DR 48 date and time 2 for Modbus SIWAREX WP231 Manual 07 2014 A5E31238908A 02 131 ...
Страница 132: ......
Страница 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Страница 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Страница 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...