Modbus communication
A.9 Modbus holding registers tables
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
214
Operating Instructions, 08/2017, A5E37367739-AC
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units regis-
ter)
Value range /
Setting options
Access
level
8899
Unsigned / 2 NAMUR status
signals
Bit encoded selection
of NAMUR status sig-
nals which impacts the
status output.
Applicable if Status
mode = 0. NAMUR
status is derived from
Alarm class (8858).
0
•
Bit 0: Out of specifi-
cation (PA, PW)
•
Bit 1: Failure (MA)
•
Bit 2: Maintenance
required (MR, MD)
•
Bit 3: Function check
(FC)
Read /
write
8842
Unsigned / 4 Alarm items 1
Bit encoded selection
of alarm items that
impact the output.
Mainly sensor alarms.
(Page 295). Applicable
if Status mode = 1.
0
Read /
write
8844
Unsigned / 4 Alarm items 2
Bit encoded selection
of alarm items that
impact the output.
Mainly sensor alarms.
(Page 295). Applicable
if Status mode = 1.
0
Read /
write
8848
Unsigned / 4 Alarm items 4
Bit encoded selection
of alarm items that
impact the output. See
(Page 295). Applicable
if Status mode = 1.
0
Read /
write
8850
Unsigned / 4 Alarm items 5
Bit encoded selection
of alarm items that
impact the output. See
(Page 295). Applicable
if Status mode = 1.
0
Read /
write
8856
Unsigned / 4 Alarm items 8
Bit encoded selection
of alarm items that
impact the output. See
(Page 295). Applicable
if Status mode = 1.
0
Read /
write
10056
Unsigned / 4 Alarm items 9
Bit encoded selection
of alarm items that
impact the output. See
(Page 295). Applicable
if Status mode = 1.
0
Read /
write