Modbus communication
A.9 Modbus holding registers tables
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
136
Operating Instructions, 08/2017, A5E37367739-AC
Modbus
register
Data type /
Size in bytes
Parameter
Description
Default value
[units]
(units regis-
ter)
Value range /
Setting options
Access
level
9129
Unsigned / 2 Digital input
signal CH3
Detected logical level
at channel 3
-
0 - 1
Read
only
9303
Float / 4
Loop current
CH4
Calculated current at
output channel 3
-
[mA]
Read
only
9400
Float / 4
Output frequen-
cy CH4
Calculated frequency
at output channel 4
-
[Hz]
Read
only
9469
Float / 4
Amount on CH4 Current totalized
amount according to
pulse output channel 4
-
(Mass: 7400 /
Volume: 7500
/ Standard
Volume:
7964)
Read
only
9340
Unsigned / 2 Status output
CH4
Calculated status at
output channel 4
-
0 - 1
Read
only
10603
Float / 4
Input current
CH4
Measured current at
input channel 4
-
[mA]
Read
only
9329
Unsigned / 2 Digital input
signal CH4
Detected logical level
at channel 4
-
0 - 1
Read
only
3072
Float / 4
Input current
CH5
Measured current input
value on channel 5
-
[mA]
-
Read
only
3074
Float / 4
Input current
CH6
Measured current input
value on channel 6
-
[mA]
-
Read
only