Parameters
SITRANS F M TRANSMAG 2
Operating Instructions, 11/2009, A5E00102775-07
87
5.2.4
Device ID
Clear device identification;
corresponds to HART long address
(device-specific
HART long
address)
1 ... 99 999 (Can only be
set with factory code by
HART)
5.2.5
Manuf. Date
Transmitter manufacture date; form:
DDMMYY
(device-specific
manufacture
date)
DDMMYY (Can only be set
with factory code by
HART)
5.2.6
Sensor
Input only possible if no data can be read
from SmartPLUG
5.2.6.1
Nom.Diameter
5
Diameter
Inside nominal diameter of the sensor with
probes: interior diameter of the
surrounding tube
(nominal width)
0.1 m
DN2 ... 2000 / 0.5 ... 80 in,
probe
(Only after ’Probe’ is
selected:) 0,1 ... 5 m
5.2.6.2
Product Type
4
Sensor order number
(7ME5034
-xxxxx-xxA0)
from SmartPLUG
5.2.6.2
Analog
Transmag
5
Select ’Yes’ for measuring sensors with
an R100 constant
In this case, a CFH value must be entered
in the 6.7.2 menu according to the
following formula:
CFH = 176,715 * DN2/R100,
DN = nominal diameter in mm)
No
•
No
•
Yes
5.2.6.3
Serial Number
4
Serial number of sensor
(serial number) From SmartPLUG
4)
Parameters apply only to devices with 20 mA/Hart communication and digital output 2 (7ME504x-0xxxx)
5)
Parameters apply only to devices with 20 mA/Hart communication and digital input (7ME504x-2xxxx)
Service
Table A- 6
Function group Service parameters
6.1
Enter Code
Input of code number agreed under
"Customer Code" (menu 6.2) for releasing
local parameterization
0
0 ... 9999
(according to setting
under menu 6.2)
6.2
Customer Code Selection of personal code:
•
Code 0: Parameters are not protected
by a code.
•
Code >0: Parameters can only be
changed after entering the code under
"Enter Code" (menu 6.1)
0
0 ... 9999
6.3
Service Code
Input of factory code for extended service
functions
0
0 ... 99999
6.4
Reset
Device reset (without parameter changes) Cancel
•
Cancel
•
Reset
6.5
Control Values
6.5.1
Volt. Um
Volt. Uref
Control value for magnetic field current
Control value for reference voltage
6.5.2
Volt. Usig
Electrode differential voltage
Содержание SITRANS F M TRANSMAG 2
Страница 1: ...Electromagnetic Flowmeters SITRANS F M TRANSMAG 2 Operating Instructions 11 2009 SITRANS F ...
Страница 2: ......
Страница 10: ...Safety notes 2 2 Laws and directives SITRANS F M TRANSMAG 2 8 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 14: ...Description 3 4 BUS Communication SITRANS F M TRANSMAG 2 12 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 40: ...Commissioning 6 4 Operating examples SITRANS F M TRANSMAG 2 38 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 92: ...Parameters SITRANS F M TRANSMAG 2 90 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 108: ...Profibus Communication B 9 Literature list SITRANS F M TRANSMAG 2 106 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 110: ...Appendix C 2 Accessories and spare parts SITRANS F M TRANSMAG 2 108 Operating Instructions 11 2009 A5E00102775 07 ...