Parameters
SITRANS F M TRANSMAG 2
84
Operating Instructions, 11/2009, A5E00102775-07
3.3.2
Engr. Unit
Engineering unit of volume
or
Engineering unit of mass
When you select a unit of mass, entry of
the actual medium density is mandatory
(menu 3.1.4)
DN 2...12: l
DN >12: m
3
•
l, hl, m
3
, Ml, ft
3
, Gal,
MGal, ImpGal,
MImpGal
•
kg, t, g, lb
3.3.3
Alarm Limit
-1 000 000 l
-108 to +108
3.4
Total. net
Totalizer forw./rev.
3.4.1
Set net
Reset totalizer to zero and stop or start
Cancel 1,2
Totalize 3
•
Cancel 1,2,
•
Reset+Stop,
•
Reset+Start 1,2,
•
Totalize 3
3.4.2
Engr. Unit
Engineering unit of volume
or
Engineering unit of mass
When you select a unit of mass, entry of
the actual medium density is mandatory
(menu 3.1.4).
DN 2...12: l
DN >12: m
3
•
l, hl, m
3
, Ml, ft
3
, Gal,
MGal, ImpGal,
MImpGal
•
kg, t, g, lb
3.4.3
Lo Alarm Limit Lower alarm limit (the lower alarm limit
must be smaller than the upper limit.)
-1 000 000 l -
Frequency 108 ... +108
3.4.4
Hi Alarm Limit
Upper alarm limit (the upper alarm limit
must be greater than the lower limit.)
+1 000 000 l
-108 ... +108
3.4.5
Hysteresis
Hysteresis for limit values
0 l
0 ... +108
(Unit the same as the
counter unit in the menu
3.4.2)
Device Outputs
Table A- 4
Function group Device outputs parameters
4.1
Analog Out
1, 2
Analog output 4 to 20mA with HART
communication
4.1.1
Current limit
Upper limit of analog current
22 mA
20 ... 22.5mA
4.1.2
Error signal
Output current in case of failure.
With the setting "Hold ..s" a current of 3.6
mA is only output in the case of a longer
failure, shorter failures are bridged with
output of the last valid current
3.6 mA
•
3.6mA, 22mA, 24mA,
•
Hold continuous,
•
Hold 5s, 20s, 40s, 60s,
120s, 240s
4.1.3
Current range
Selecting the current range at the analog
output on which the measuring range
(menu 3.1.2) is shown.
For the setting 0 to 20 mA the failure
signal (menu 4.1.2) must be set to 22 or
24 mA.
4 ... 20 mA
•
4 ... 20 mA;
•
0 ... 20 mA
Содержание SITRANS F M TRANSMAG 2
Страница 1: ...Electromagnetic Flowmeters SITRANS F M TRANSMAG 2 Operating Instructions 11 2009 SITRANS F ...
Страница 2: ......
Страница 10: ...Safety notes 2 2 Laws and directives SITRANS F M TRANSMAG 2 8 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 14: ...Description 3 4 BUS Communication SITRANS F M TRANSMAG 2 12 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 40: ...Commissioning 6 4 Operating examples SITRANS F M TRANSMAG 2 38 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 92: ...Parameters SITRANS F M TRANSMAG 2 90 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 108: ...Profibus Communication B 9 Literature list SITRANS F M TRANSMAG 2 106 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 110: ...Appendix C 2 Accessories and spare parts SITRANS F M TRANSMAG 2 108 Operating Instructions 11 2009 A5E00102775 07 ...