Technical data
10.2 Dimensions
SITRANS F M TRANSMAG 2
76
Operating Instructions, 11/2009, A5E00102775-07
Local display
Table 10- 7 Display
General display
LCD, background illumination, two lines with16 characters
each
Multi-display
For flow, quantity, flow velocity
Keypad
4 operating elements for entering parameters
Power supply
Table 10- 8 Power supply
AC voltage
AC 100 to 250 V, ±15 %, 47 to 63 Hz
Power consumption
Approx. 120 to 630 VA, dependent on sensor
Power failure
Bridging of at least 1 power supply cycle (> 20 ms)
Line fuse
AC 100 to 230 V: T1.6A
Magnetic current fuse
F5A/250 V
10.2
Dimensions
90
(3.54)
70
(2.76)
90
(3.54)
150 (5.91)
95 (3.74)
Figure 10-1 SITRANS FM Transmag 2 transmitter (remote design) with standard mounting plate
Содержание SITRANS F M TRANSMAG 2
Страница 1: ...Electromagnetic Flowmeters SITRANS F M TRANSMAG 2 Operating Instructions 11 2009 SITRANS F ...
Страница 2: ......
Страница 10: ...Safety notes 2 2 Laws and directives SITRANS F M TRANSMAG 2 8 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 14: ...Description 3 4 BUS Communication SITRANS F M TRANSMAG 2 12 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 40: ...Commissioning 6 4 Operating examples SITRANS F M TRANSMAG 2 38 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 92: ...Parameters SITRANS F M TRANSMAG 2 90 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 108: ...Profibus Communication B 9 Literature list SITRANS F M TRANSMAG 2 106 Operating Instructions 11 2009 A5E00102775 07 ...
Страница 110: ...Appendix C 2 Accessories and spare parts SITRANS F M TRANSMAG 2 108 Operating Instructions 11 2009 A5E00102775 07 ...