Messages and diagnostics
9.9 Self-test (user-test)
SIRIUS 3RW52 Soft Starter
190
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Position of the rotary coding
switch "Rated operational
current I
e
of the motor"
LED
"RN"
"ER"
"MT"
"STATE /
OVER-
LOAD"
"RESET
MODE"
"SOFT
TORQUE"
13
Flickers
green
Off
Lights up
yellow
Lights up
green
Off
Lights up
green
14
Flickers
green
Off
Lights up
yellow
Lights up
green
Lights up
green
Off
15
Flickers
green
Off
Lights up
yellow
Lights up
green
Lights up
green
Lights up
green
16
Flickers
green
Lights up red
Off
Off
Off
Off
Current detection test
LED
Display of test result
pass
fail
"STATE / OVERLOAD"
Flickers red
Off
In case of error: System LEDs
(RN, ER, MT) flashing.
Device error, replace device.
Motor overload protection test
Display of test result
pass
fail
"STATE / OVERLOAD" LED
Flashes red
Off
In case of error: System LEDs
(RN, ER, MT) flashing.
Device error, replace device.
"ER" LED
Flashes red
In case of error: System LEDs
(RN, ER, MT) flashing.
Device error, replace device.
Error signaling output
Active
Not active
Contact blocks / motor
Deactivated
Unchanged
Self-test of the 3RW5 HMI High Feature
You will find more information on the self-test of the 3RW5 HMI High Feature in Chapter
Execute HMI diagnostics with the 3RW5 HMI High Feature (Page 185).