Parameter assignment
6.11 Parameterize analog output AQ via the 3RW5 HMI High Feature
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
121
6.11
Parameterize analog output AQ via the 3RW5 HMI High Feature
Operating principle
You can re-parameterize the output of the analog output with the 3RW5 HMI High Feature.
The actual average phase current L1 - L3 of the motor is displayed in % at the external
evaluation unit via the analog output. Depending on the respective connecting terminal being
used, the signal can be displayed either as current or voltage.
Ⴠ
Terminals: AQ- / AQ I+
Measuring range of current output: 4 - 20 mA
Ⴠ
Terminals: AQ- / AQ U+
Measuring range of voltage output: 0 - 10 V
Requirements
Ⴠ
3RW5 HMI High Feature (accessory)
Menu: "Parameters > Soft Starter > Analog output"
Ⴠ
Access protection to 3RW5 HMI High Feature is not active or has been reset
Ⴠ
Device version with analog output
Ⴠ
Evaluation unit is connected properly (Page 232).