Maintenance and servicing
10.4 Restore factory setting
SIRIUS 3RW52 Soft Starter
200
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Procedure
1.
Make sure that the motor is switched off and that you do not start the motor while
restoring the factory settings.
To ensure the quickest and most fault-free restoration of the factory setting, it is
recommended that you disconnect the main voltage (operating voltage) at the
3RW52 soft starter.
2.
Restore the factory settings.
The following procedures are possible:
–
With the MODE and RESET / TEST (Page 203) keys.
–
Via the 3RW5 HMI High Feature (accessory):
Restoring the factory settings via High Feature 3RW5 HMI (Page 201)
Restoring the factory settings with the Master RESET button via
3RW5 HMI High Feature (Page 202)
–
Via the local interface on the 3RW5 HMI High Feature with SIRIUS Soft Starter ES
(TIA Portal)
Brief overview: Window "Project Navigation" with current project under created
Soft Starter > "Commissioning" > Window "Work area" > "Soft Starter > Functions >
Commands > Factory settings"
–
With a fieldbus via a 3RW5 communication module with SIRIUS Soft Starter ES
(TIA Portal) Premium / Professional (only via a 3RW5 PROFINET or
PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via local interface on the
3RW5 HMI High Feature
–
With a fieldbus via a 3RW5 communication module with the command
"Factory settings" in data set 93 (only via a 3RW5 PROFINET or
PROFIBUS communication module):
–
With a fieldbus via a 3RW5 communication module with the configuration software of
the control (only via a 3RW5 PROFINET or EtherNet/IP communication module). Only
the communication parameters are reset here.
Result
The factory setting of the selected device or all devices is restored.