Parameter assignment
6.12 Parameterizing the High Feature 3RW5 HMI
SIRIUS 3RW52 Soft Starter
124
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
6.12
Parameterizing the High Feature 3RW5 HMI
Requirements
Ⴠ
3RW5 HMI High Feature (accessory)
Setting options
Ⴠ
3RW5 HMI High Feature
Menu: "Parameters > HMI"
Access protection to the 3RW5 HMI High Feature is not active or has been reset.
Ⴠ
With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created
Soft Starter > "Parameters" > Window "Work area" > "HMI"
Ⴠ
With a fieldbus via a 3RW5 communication module:
–
With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
(only via a 3RW5 PROFINET or PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
–
Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
–
User program
You can find further information on the parameters that can be set via the fieldbus in the
manual of the respective 3RW5 communication module.
Parameters
Parameter
Description
Local interface activated
(can only be set via
3RW5 HMI High Feature)
The parameter is only visible if the local interface is enabled (factory setting).
Disables the local interface of the 3RW5 HMI High Feature.
Before you can connect a PC with SIRIUS Soft Starter ES (TIA Portal) to the
3RW52 soft starter via the local interface, the local interface must be enabled. You can
prevent unauthorized access via SIRIUS Soft Starter ES (TIA Portal) by disabling the local
interface.
Local interface deactivated
(can only be set via
3RW5 HMI High Feature)
The parameter is only visible if the local interface is disabled.
Enables the local interface of the 3RW5 HMI High Feature.
Timer lighting dark
If no keys on the 3RW5 HMI High Feature are pressed, the display will shut down after a
specified time period has elapsed. The setting "0 min" deactivates shutdown of the display.
x
Factory setting: 5 min
x
Setting range: 0 ... 60 min
x
Increment: 1 min