Parameter assignment
6.7 Parameterize output 13, 14 (output signal ON or RUN)
SIRIUS 3RW52 Soft Starter
106
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
6.7
Parameterize output 13, 14 (output signal ON or RUN)
Operating principle
One of these two states is output at output 13, 14:
Ⴠ
ON (factory setting)
Ⴠ
RUN
You will find further information in chapters Operating principle (Page 28) and State
diagrams of the inputs and outputs (Page 79).
Use the output function ON, for instance, to implement latching if you selected pushbutton
control.
Use the Output function RUN in order, for instance, to control a line contactor connected
upstream.
Requirements
Ⴠ
Supply voltage (control supply voltage) is present.
Ⴠ
The 3RW52 soft starter does not signal any faults, the LED STATE / OVERLOAD is off.
Video instructions
Video instructions can be found in SIOS
(
https://support.industry.siemens.com/cs/ww/en/view/109778873
):