Example circuits
A.2 Control circuit connection
SIRIUS 3RW52 Soft Starter
226
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
A.2.4
Control by PLC
Requirements
Utilization of a 3RW52 soft starter..-...4 (24 V) and power supply with DC voltage.
WARNING
Automatic restart.
Can cause death or serious injury.
If a starting command is pending, a restart will be triggered automatically after the reset.
This particularly applies if the motor protection has tripped. Dangerous states of the system
can result.
Reset the start command (e.g. via the PLC or switch) before performing a reset.
To do this, for example, link the group error output (terminals 95 and 96) into the control.