Functions
8.12 High Feature 3RW5 HMI
SIRIUS 3RW52 Soft Starter
154
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
8.12
High Feature 3RW5 HMI
Observe the hardware configuration in Chapter Design and operator controls of the
High Feature 3RW5 HMI (Page 111).
8.12.1
Monitoring
8.12.1.1
Monitoring the measured values of the 3RW52 soft starter with the
3RW5 HMI High Feature
Requirements
Ⴠ
3RW5 HMI High Feature (accessory)
Menu: "Monitoring > Measured values"
Operating principle
The measured values are provided by the respective device functions. Current measured
values are stored in the measured value memory. These values can be read out and
evaluated by the 3RW5 HMI High Feature. You can specify up to 5 measured values, which
are shown on the operation display (Page 124).
Further display options of the measured values
Ⴠ
With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created
Soft Starter > "Commissioning" > Window "Work area" > "Soft Starter >
Measured values"
Ⴠ
With a fieldbus via a 3RW5 communication module:
–
With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
(only via a 3RW5 PROFINET or PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
–
Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
–
User program