Data sets for the 3RA64/3RA65 compact starter with IO-Link
A.5 Group diagnostics - data set (index) 90
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
301
Starter 4
Table A- 8
Data set (index) 90 - starter 4
Data set
Byte.Bit
Designation
Index
Specific module diagnostics - starter 4
90
36.0...36.6
Starter 4 (item number)
90
37.0
Reserved
90
37.1
Starter available
90
37.2
Reserved
Specific diagnostics - starter 4
90
42.0
Contact block defective
90
42.1
Contact block supply voltage missing
90
42.2
Reserved
90
42.3
Motor overload tripping
90
42.4
Circuit breaker tripped
90
42.5
Switch off - end position right
90
42.6
Switch off - end position left
90
42.7
Process image error
90
43.0
Manual operation local
90
43.1
Manual operation connection aborted
90
43.2
Contact block cooling time active
90
43.3
Remaining life time (RLT 0%)
Operator panel
Table A- 9
Data set (index) 90 - operator panel
Data set
Byte.Bit
Designation
Index
Specific module diagnostics - operator panel
90
45.0..45.6
Operator panel (item number)
90
46.1
Operator panel available
For additional information, please refer to "Process image (Page 111)".
Содержание Sirius 3RA6
Страница 2: ......
Страница 14: ...Introduction SIRIUS 3RA6 compact starter 14 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 266: ...Technical data 9 5 8US busbar adapter SIRIUS 3RA6 compact starter 266 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 310: ...References B 1 References SIRIUS 3RA6 compact starter 310 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 314: ...Glossary SIRIUS 3RA6 compact starter 314 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 319: ......