Accessories
7.12 AS-i mounting module for 3RA61/3RA62 compact starter
SIRIUS 3RA6 compact starter
214
System Manual, 09/2014, NEB560060102000/RS-AA/006
7.12.5
Connection
7.12.5.1
Connecting the AS-i mounting module
To enable communication via an AS-Interface, the AS-i mounting module must first be
installed on the compact starter (24 V). Then the AS-i mounting module can be connected to
the AS-Interface using the AS-i cable.
7.12.5.2
Connecting the AS-Interface
Connection method
The following cables are required:
●
AS-Interface cable.
●
24 VDC AUX PWR cable for supplying the final controlling element
In order for the cables to be secured within the connectors, they must have a conductor
cross-section of 2 x (0.5 ... 0.75) mm
2
.
ESD directives
ESD components are destroyed by voltage and energy far below the limits of human
perception. Voltages of this kind occur as soon as a device or an assembly is touched by a
person who is not electrostatically discharged. ESD components which have been subject to
such voltage are usually not recognized immediately as being defective, because the
malfunction does not occur until after a longer period of operation.
NOTICE
Damage to the AS-i mounting module from electrostatic charging!
The AS-i mounting contains components sensitive to electrostatic charge. These modules
will be destroyed or damaged by improper handling.
•
You must discharge your body electrostatically immediately before touching an
electronic component. To do this, touch a conductive, grounded object, e.g., a bare
metal part of a switch cabinet or the water pipe.
•
Always hold the component by the plastic enclosure.
•
Electronic modules should not be brought into contact with electrically insulating
materials such as plastic film, plastic parts, insulating table supports or clothing made of
synthetic fibers.
•
Always place electrostatic sensitive devices on conductive bases.
•
Always store and transport electronic modules or components in ESD-safe conductive
packaging, e.g. metallized plastic or metal containers. Leave the component in its
packaging until installation.
Содержание Sirius 3RA6
Страница 2: ......
Страница 14: ...Introduction SIRIUS 3RA6 compact starter 14 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 266: ...Technical data 9 5 8US busbar adapter SIRIUS 3RA6 compact starter 266 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 310: ...References B 1 References SIRIUS 3RA6 compact starter 310 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 314: ...Glossary SIRIUS 3RA6 compact starter 314 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 319: ......