3RA64/3RA65 compact starter with IO-Link
6.9 Connection
SIRIUS 3RA6 compact starter
128
System Manual, 09/2014, NEB560060102000/RS-AA/006
Pin assignment
The following pin assignment applies for the 3RA65 compact starter (reversing starter) with
IO-Link with screw-type or spring-loaded terminals.
Terminals
Description
Image
1L1, 3L2, 5L3
Main contacts (line side)
L+
Supply voltage for IO-Link
C/Q
Communication signal / DI/DO
L-
Ground IO-Link
A2-
Auxiliary voltage -
A1+/Y1
Auxiliary v / limit
(direction of rotation 1)
Y2
Auxiliary voltage - (direction of
rotation 1)
Y3
Limit (direction of
rotation 2)
Y4
Auxiliary voltage - (direction of
rotation 2)
2T1, 4T2, 6T3
Main contacts (on the outgoing
side)
①
Conductor bridge pre-mounted at
factory
Note
Before a limit switch can be connected to terminals Y1 - Y2 or Y3 - Y4, the bridge must be
removed.