3RA61/3RA62 compact starter
5.3 Functions
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
55
When the actuator is in the READY position, the 3RA62 compact starter (reversing
starter) can adopt the following statuses:
Table 5- 4
Actuator display elements READY (3RA62 compact starter)
Actuator
LEDs
Compact starter status
A1/A2
B1/B2
ON I 1
ON I 2
READY
OFF
OFF
OFF
Compact starter is ready:
•
The circuit breaker mechanism is switched on.
•
Control supply voltage not present.
•
All main contacts are open.
READY
GREEN
GREEN
OFF
Compact starter is switched on:
•
The circuit breaker mechanism is switched on.
•
Control supply voltage is present.
•
The main contacts "direction of rotation 1" are
closed.
READY
GREEN
OFF
GREEN
Compact starter is switched on:
•
The circuit breaker mechanism is switched on.
•
Control supply voltage is present.
•
The main contacts "direction of rotation 2" are
closed.
READY
GREEN
OFF
OFF
There is a fault.
•
"Overload trip" display white: Overload tripped.
•
"Overload trip" display not white:
–
Control supply voltage is outside the working
range.
–
Control supply voltages for both directions of
rotation were applied simultaneously.
–
Polarities are reversed in the case of
DC connection.
•
All main contacts are open.
Содержание Sirius 3RA6
Страница 2: ......
Страница 14: ...Introduction SIRIUS 3RA6 compact starter 14 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 266: ...Technical data 9 5 8US busbar adapter SIRIUS 3RA6 compact starter 266 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 310: ...References B 1 References SIRIUS 3RA6 compact starter 310 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 314: ...Glossary SIRIUS 3RA6 compact starter 314 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 319: ......