Accessories
7.12 AS-i mounting module for 3RA61/3RA62 compact starter
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
229
Undervoltage and overvoltage detection
If an undervoltage or overvoltage is detected when an AS-i output bit (D0 or D1) is set, the
compact starter switches off. The compact starter can only be switched on again when the
AUX PWR returns to the normal range of 24 V ± 20% and the AS-i output bit (D0 or D1) has
been reset.
Undervoltage detection
takes place via
Overvoltage detection
takes place via
Compact starter not
controlled
the AS-i mounting module from approx.
24 V - 20%
the AS-i mounting module from
approx. 24 V + 20%
Compact starter
controlled
the compact starter.
AS-i mounting module is deactivated.
the AS-i mounting module from
approx. 24 V + 20%