3RA64/3RA65 compact starter with IO-Link
6.7 Diagnostics
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
119
Compact starter status
3RA65 (reversing starter)
3RA64 (direct starter)
Actuator
DEVICE
STATE / ON 1
SF RLT 0%
1
(DO0.0)
2
(DO0.1)
Process image error
READY
Yellow
Off
Red
Off
Green
Green
Error messages
The device is defective
X
Red
X
Red
Off
X
X
IO-Link power supply missing
1)
X
Flashing
red
X
Red
Off
X
X
Short-circuit function
Short circuit tripped
TRIPPED
X
Off
Red
Off
X
X
Overload tripping
Overload tripped (3RA64)
READY
Flashing
yellow
Off
Red
X
X
X
Overload tripped direction of
rotation 1
READY
Yellow
Off
Red
Off
Green
Off
Overload tripped direction of
rotation 2
READY
Yellow
Off
Red
Off
Off
Green
Limit function
Limit switch tripped (3RA64)
Ready/
Direction 1
READY
Green/
Yellow
Off
Red
Off
X
X
Limit switch 1 tripped and direction
of rotation 1 triggered
READY
Yellow
Off
Red
Off
Green
Off
Limit switch 1 tripped and opposite
direction 2 triggered
READY
Green
Green
Red
Off
Off
Green
Limit switch 2 tripped and direction
of rotation 2 triggered
READY
Yellow
Off
Red
Off
Off
Green
Limit switch 2 tripped and opposite
direction 1 triggered
READY
Green
Green
Red
Off
Green
Off
Содержание Sirius 3RA6
Страница 2: ......
Страница 14: ...Introduction SIRIUS 3RA6 compact starter 14 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 266: ...Technical data 9 5 8US busbar adapter SIRIUS 3RA6 compact starter 266 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 310: ...References B 1 References SIRIUS 3RA6 compact starter 310 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 314: ...Glossary SIRIUS 3RA6 compact starter 314 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 319: ......