Current setting I
e
Set the operating current of the motor to be protected on the setting scale.
Figure 5-5
Setting the current setting I
e
on the compact starter
RESET M/A
Select manual or auto reset following an overload trip on the "RESET M/A"
(manual/automatic) selector switch:
●
Manual reset: Following overload trip, set the 3RA61/3RA62 compact starter manually
using the blue reset button.
●
Auto reset: Following an overload trip, the 3RA61/3RA62 compact starter is reset
automatically after 3 minutes. However, a manual reset can still be performed if you have
selected this setting.
Figure 5-6
Setting RESET M/A on the compact starter
For additional information on the manual and auto reset functions, please refer to "Overload
protection function (Page 57)".