2.4 Measured value processing
37
6MD665 Manual
C53000-G1876-C103-3
2.4.4.3
Settings
2.4.4.4
Information
2.4.5
Measurement I 1.packet
This packet serves to measure an individual current. The function provides the r.m.s.
value of the fundamental component.
2.4.5.1
Description
The frequency of the current is determined from the input signal. If it falls below 10%
of the rated value, the frequency is marked as invalid. The rated value of the frequency
is taken from
36\VWHP'DWD
.
Routing of the measurement input to the respective measured value channel Current
and the routing of the measuring results is performed with DIGSI
®
.
Specifications for secondary transformer current are made in the properties dialog box
of
08,B
.
Information on allocation can be obtained from the SIPROTEC
®
system description /
2.4.5.2
Configuration Notes
6HF&XUU1RP9DO
The secondary factory-preset rated transformer current can be set in the predefined
range.
2.4.5.3
Settings
Addr.
Parameter
Setting Options
Default Setting
Description
0
SecVoltgNomVal
0.00 .. 200.00 V; <
> 0
100.00 V
Secondary Voltage Nominal
Value
No.
Message
Type of Information
Description
-
Input U/I
MK
Voltage or Current Input U/I
-
U
MW
Voltage U
-
f
MW
frequency
Addr.
Parameter
Setting Options
Default Setting
Description
0
SecCurrNomVal
0.00 .. 5.00 A; < >
0
1.00 A
Secondary Current Nominal
Value
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...