2 Functions
76
6MD665 Manual
C53000-G1876-C103-3
Accepting settings
To apply your settings, click OK. The Properties - IRC combination dialog box is
closed.
Allocating information of the individual devices involved
The purpose of the IRC combination is to distribute process information between
SIPROTEC
®
4 devices. You must therefore make the following decisions for each
SIPROTEC
®
4 device participating in an IRC combination:
• Which process information from the SIPROTEC
®
4 device should be made avail-
able to the other devices in the IRC combination?
• Which process information from the SIPROTEC
®
4 device should be assignable to
process information received from the IRC combination?
You make this selection for each SIPROTEC
®
4 device individually in the DIGSI
®
allo-
cation matrix.
Open the SIPROTEC device with the DIGSI
®
device processing function. Double-click
the object Allocate to display the device matrix.
IRC columns
One column with the name O is provided in the device matrix for the IRC combination
as source and IRC combination as destination. These columns are fundamentally
only visible when the functionality of the IRC has been defined in the device model.
These columns are shielded as soon as you select the information filter Only com-
mands. This is explained by the fact that commands cannot be swapped within an
IRC combination.
Allocable Information
types
The following information types can be allocated within an IRC combination:
• Single point indication (only SI, not SI_F)
• Double point indication (only OI, not OI_F)
• Internal single indication (only IS, not IS_F), can only be allocated as destination,
use as SI source
• Internal double point indication
• Bit pattern indication
• Transformer tap indication
• Limit value
• User-defined limit value
• Measured value
• User-defined measured value
• External counter
Routing information
to the IRC source
Information that is routed to IRC as source can be assigned to information of other
users of the IRC combination during the course of the run process. Information
received from an IRC combination is represented within the SIPROTEC
®
4 device by
information specific to this device. The assignment between received information and
device-specific information takes place with the combination matrix.
Routing information
to the IRC destina-
tion
Information that is routed to IRC as destination can be forwarded to other users of
the IRC combination. This forwarding procedure is also defined using the combination
matrix.
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...