3 Installation and Commissioning
110
6MD665 Manual
C53000-G1876-C103-3
For mounting the device proceed as follows:
• Tighten the device by means of 6 screws. The dimensional drawing can be found
in the Technical data section. Use self-furrowing screws M5 in 2 mm steel plates or
inner thread M5.
• Connect the ground on the rear plate of the device to the protective ground of the
panel. Using at least one M4 screw. The cross-sectional area of the ground wire
must be equal to the cross-sectional area of any other control conductor connected
to the device. The cross-section of the ground wire must be at least 2.5 mm
2
.
• Connections are realised via the plug terminals or screw terminals on the rear side
of the device according to the circuit diagram. When using forked lugs for direct con-
nections or screw terminal, the screws, before having inserted the lugs and wires,
must be tightened in such a way that the screw heads are even with the terminal
block. A ring lug must be centred in the connection chamber, in such a way that the
screw thread fits in the hole of the lug. The SIPROTEC
®
system description /1/ has
pertinent information regarding wire size, lugs, bending radii, etc.
For mounting the operator panel please observe the following:
• Remove the 4 covers on the corners of the front plate. This exposes the 4 elongated
holes in the mounting bracket.
• Insert the operator panel into the panel cut-out and fasten with four screws. The
dimensional drawing can be found in the Technical data section.
• Mount the four covers.
• Connect the ground on the rear plate of the operator control element to the protec-
tive ground of the panel using at least one M4 screw. The cross-sectional area of
the ground wire must be equal to the cross-sectional area of any other control con-
ductor connected to the device. The cross-section of the ground wire must be at
least 2.5 mm
2
.
• Connect the operator panel to the device. Furthermore, plug the 68-pin connector
of the cable belonging to the operator panel into the corresponding connection at
the rear side of the device (see SIPROTEC
®
system description /1/).
3.1.3.4
Mounting without operator panel
For mounting the device proceed as follows:
• Tighten the device by means of 6 screws. The dimensional drawing can be found
in the Technical data section. Use self-furrowing screws M5 in 2 mm steel plates or
inner thread M5.
• Connect the ground on the rear plate of the device to the protective ground of the
panel. Using at least one M4 screw. The cross-sectional area of the ground wire
must be equal to the cross-sectional area of any other control conductor connected
to the device. The cross-section of the ground wire must be at least 2.5 mm
2
.
• Connections are realised via the plug terminals or screw terminals on the rear side
of the device according to the circuit diagram. When using forked lugs for direct con-
nections or screw terminal, the screws, before having inserted the lugs and wires,
must be tightened in such a way that the screw heads are even with the terminal
block. A ring lug must be centred in the connection chamber so that the screw
thread fits in the hole of the lug. The SIPROTEC
®
system description /1/ has perti-
nent information regarding wire size, lugs, bending radii, etc.
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...