2.5 Metered Value Processing
45
6MD665 Manual
C53000-G1876-C103-3
Select the tab Restore trigger and energy flow direction and enter the restore
trigger and energy flow direction.
Select the Cyclic option if the metered value is to be transmitted to the control center
at cyclic intervals. Otherwise select the None option. By pressing the Settings button,
you end up in the dialog box for setting the corresponding time interval. One minute
is preset.
Note
The settings made in the Cyclical restoring tab apply globally for all metered values.
Under Energy flow direction, you define whether the metered value summates the
quantity of exported or imported energy by selecting one of the two options.
Figure 2-13
Object properties dialog box, Restore trigger and energy flow direction tab
Select the tab Pulse type and error input and make your settings there.
Select the Wiping pulse / S0 option if the rising edge of a single pulse is to increment
the metered value by one. Select the Double current pulse option if the falling edge
of a double current pulse is to increment the metered value by one.
As soon as you route a pulse metered value to a binary input, the next binary input can
be automatically routed as an fault input. A signal to this fault input can mark the count
as corrupt. If you use this procedure, select the Use fault input checkbox. If it is not
selected, the binary input following the metered pulse input is available to another
application.
Figure 2-14
Object properties dialog box, Pulse type and error input tab
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...