3 Installation and Commissioning
106
6MD665 Manual
C53000-G1876-C103-3
Figure 3-7
Location of the jumpers for configuring the PROFIBUS interface terminating
resistors
Termination resistors for the PROFIBUS interface can also be implemented externally
(e.g. on the connection module). In this case the termination resistors on the PROFI-
BUS interface module must be disconnected.
Figure 3-8
Termination of the RS485 interface (external)
The R485 interface can be converted into an RS232 interface by modifying the setting
of the appropriate jumpers.
The jumpers X5 to X10 must be plugged in the same way.
When the device is delivered from the factory, the jumper setting corresponds to the
configuration ordered and need not be changed.
Jumper X5 X6 X7 X8 X10 X11 X12 X13
RS232 1–2 1–2 1–2 1–2 1–2 2–3 1–2 1–2
RS485 2–3 2–3 2–3 2–3 2–3 2–3 1–2 1–2