Diagnostics data
6.1 Diagnostics by means of LED displays
SIMOTION D410
Commissioning Manual, 02/2012
199
Meaning
RDY
RUN/STOP OUT > 5V
SF/BF:
Bus error
•
PROFIBUS master: At least one slave is missing
•
PROFIBUS slave: No parameter assignment master found
•
PROFINET: Failure of a connected I/O device; at least one of the
assigned I/O devices cannot be addressed; faulty or missing
configuration data.
Priority: 2
1)
x
x
x
2/1
(red)
Sublicensing of technology/option objects
Priority: 3
1)
x
x
x
0.5/1
(red)
Upgrade/downgrade operation running.
0.5/1
(yellow)
x
x
x
The upgrade/downgrade operation has completed
(power OFF/ON of the upgraded/downgraded devices is necessary)
2/1
(yellow)
x
x
x
Transition from STOP/STOPU to RUN
x
2/1
(green)
x
x
STOP/STOPU
x
1
(yellow)
x
x
RUN
x
1
(green)
x
x
Transition
•
from RUN to STOP/STOPU
•
STOP to STOPU
•
STOPU to STOP
x
2/1
(yellow)
x
x
Memory reset requested by SIMOTION D410, or by means of mode
selector switch.
x
0.5/1
(yellow)
x
x
Memory reset in progress
x
0
x
0
Memory reset completed
x
1
(yellow)
x
x
Firmware download to the integrated PROFINET interface is busy
0
x
x
2/1
(yellow)
Firmware download to the integrated PROFINET interface is
completed SIMOTION cannot enter the RUN and Online mode
x
x
x
Λ
(red)
Upgrading SIMOTION devices (device update tool)
Upgrade/downgrade running
x
x
x
0.5/1
(green)
Upgrade/downgrade completed with error
x
x
x
Λ
(red)
Upgrade/downgrade completed without error
x
x
x
0
2)
Backing up diagnostic data and non-volatile data