7
7.2 Fault Recorders
66
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Quality tracks (binary tracks)
All tracks including quality tracks are recorded by SIMEAS R-PMU, evaluated by OSCOP P and
presented in the form of a diagram with eight tracks (one track not used). Depending on the
status, a bar (logical 1) or no bar (logical 0) is recorded.
The following status information is displayed for the recording period of time that is set on
OSCOP P:
Reference frequency invalid:
The reference is invalid (insufficient signal quality), the
measured values based on the reference frequency are also invalid.
0: Reference frequency valid
1: Reference frequency invalid
Frequency group 1 invalid:
The frequency measurement of group 1 of the evaluated DAU
is not possible or faulty, e. g., because of missing signals.
0: Frequency measurement valid
1: Frequency measurement invalid
Frequency group 2 invalid:
The frequency measurement of group 2 of the evaluated DAU
is not possible or faulty, e. g., because of missing signals.
0: Frequency measurement valid
1: Frequency measurement invalid
DAU not synchronized:
Synchronization of the evaluated DAU is not (yet) possible
because, for example, the system has not (yet) completed the transient recovery phase after
the GPS signal has been cut-off and returned, or after the SIMEAS R has been restarted.
0: Time synchronized in DAU
1: Time not synchronized in DAU
CPU not synchronized:
The CPU is not or not yet synchronized and is thus free-running
based on RTC (DCF77 signal provided only approx. 2 minutes after start-up).
0: Time synchronized in CPU
1: Time not synchronized in CPU
TAR recording active:
displays the current recording of the TAR
0: inactive: no recording
1: active: recording active
TPR recording active:
displays the current recording of the TPR
0: inactive: no recording
1: active: recording active
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...