16
16.1 Technical Data of the SIMEAS R-PMU
246
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Voltage input (VCDAU or VDAU)
All precision data refer to the rms value in stationary operation mode at nominal frequency and
at 23 °C ±1 °C.
Measuring range 1
AC 1.5 V to AC 200 V
Impedance
>100 k
Ω
Resolution
15 mV
Overvoltage
max. AC 300 V for 5 s
Precision
class 0.3
±0.25 % of measured value ±30 mV
Frequency response
3 Hz to 5500 Hz (5 %)
Number of A/D converters per channel
1
Measuring range 2
AC 3 V to AC 400 V
Impedance
>200 k
Ω
Resolution
30 mV
Overvoltage
max. AC 600 V for 5 s
Precision
class 0.3
±0.25 % of measured value ±30 mV
Frequency response
3 Hz to 5500 Hz (5 %)
Number of A/D converters per
voltage channel
1
current channel
2
Electrical isolation
up to 3.25 kV, 50 Hz
Frequency accuracy at f
n
±5 Hz
5 mHz
Current input (VCDAU or CDAU)
All precision data refer to the rms value in stationary operation mode at nominal frequency and
at 23 °C ±1 °C.
Dynamic AD and converter switching
Complete measuring range
AC 5 mA to AC 400 A
Measuring range
AC 5 mA to AC 7 A
Resolution
0.5 mA
Precision
class 0.5
0.5 % of measured value ±0.5 mA
Frequency response
3 Hz to 5500 Hz (5 %)
Measuring range
>AC 7 A to AC 200 A
Resolution
30 mA
Precision
class 1.5
1.5 % of measured value ±100 mA
Frequency response
0 Hz to 5500 Hz (5 %)
Measuring range
>AC 200 A to AC 400 A
Resolution
30 mA
Precision
class 3.5
±3.5 % of measured value
Frequency response
0 Hz to 5500 Hz (5 %)
Permanently
AC 20 A
Overload
AC 100 A, 30 s
AC 500 A, 1 s
AC 1200 A, half-wave
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...