3 System Messages
283
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
1282
2
CALL_PC Callback PC was acknowledged by
OSCOP P. Interface:
-
1283
1
CALL_PC Callback PC repeated. Interface:
Make sure that OSCOP P runs in automatic
mode and was parameterized to be able to
receive callbacks from this device.
Check the communication link and the
callback communication parameters if
necessary.
1536
2
BATTERY Start of battery monitoring process
Cyclical battery test (will be started even
without battery)
1537
2
BATTERY Start of battery monitoring after startup.
Test time:
-
1538
2
BATTERY Battery monitoring after startup OK
-
1539
0
BATTERY Fault in battery monitoring after startup.
Remaining time:
-
1542
0
BATTERY Fault in battery monitoring during operation.
Remaining time:
-
1543
2
BATTERY Continuous charging started.
Charging time:
-
1545
0
BATTERY Unable to charge battery or time-out
-
1547
1
BATTERY Battery fully discharged
-
1548
0
BATTERY Power supply failure,
battery operation active
-
1549
1
SYSTEM
Reset initiated
-
1793
2
PANEL
Panel button pressed
-
1807
1
PANEL
External reset triggered
Reset trigger via control input 3
1808
1
PANEL
Recording interrupted, as data can no
longer be disposed of
-
1810
1
SYSTEM
Device ready
Note: Some functions are ready for
operation with a delay (manual trigger,
network trigger)
1811
1
SYSTEM
Power supply OK
-
1812
2
SYSTEM
OSCOP P communication
-
1813
2
SYSTEM
TAR/Analog fault recorder:
Recording event
-
1814
2
SYSTEM
TPR/Frequency power recorder:
Recording event
-
1815
0
SYSTEM
DAU fault
DAU boot fault or DAU failure (self-
monitoring), hotline
1816
0
SYSTEM
Printer fault
Check printer, printer connection; fault
disappears after correction (takes approx. 5
minutes)
1818
1
SYSTEM
PC unreachable
Make sure that OSCOP P runs in automatic
mode and was parameterized to be able to
receive callbacks from this device.
Check the communication link and the
callback communication parameters if
necessary.
1820
1
SYSTEM
Ring buffer active
90 % of the reserved TAR or TPR memory
size is reached, the oldest data will be
deleted up to 80 %.
1821
0
SYSTEM
Temperature has risen above permissible
value of +55 °C
-
1822
0
SYSTEM
Temperature has dropped below
permissible value of -5 °C
-
Log No.
Type
Class
Description
Comment
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...