14
14.3 Extending the Existing Hardware
203
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
17. Plug the connecting line (ribbon cable) between the front plate and the CPU module into the
CPU module.
18. Screw the front plate back to the device. Be careful not to pinch the ribbon cable when
mounting the front plate.
19. Screw the knurled nut to switch S1.
20. Screw the cover back into place.
21. Connect the measuring signals to the new adapters.
22. Apply the supply voltage to the device.
23. Switch the device on using switch S1.
24. Connect a notebook to the service interface COM S at the front of the device.
25. Enable the new module using the OSCOP P system program and set the parameters for the
individual channels. For detailed information regarding the parameterization, please refer to
Chapter 12.
14.3.3
Extending a SIMEAS R-PMU by Communication Components
Communication components are analog or ISDN modems or X.25-PAD modules. They are
connected to the COM 1 interface at the rear panel of the SIMEAS R-PMU.
1. Switch the SIMEAS R-PMU off using switch S1.
2. Connect the data end device to the COM 1 interface at the rear panel of the SIMEAS R-PMU
using the appropriate cable.
3. Build up a connection between the data end device and the telephone socket.
4. Switch the data end device on.
5. Switch the SIMEAS R-PMU on using switch S1.
6. Connect a notebook to the service interface COM S at the front side of the SIMEAS R-PMU.
7. Enable the new modem using the OSCOP P system program and set the connection
parameters. For detailed information regarding the parameterization, please refer to
Chapter 12.
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...