12
12.11 Slot Description
158
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
VCDAU and coupled CDAU at star and delta connection
PSUM1-3
Total active power group 1 of the coupled CDAU
PSUM5-7
Total active power of VCDAU and group 2 of the coupled
CDAU
P4
Active power of channel 4 group 1 of the coupled CDAU
P8
Active power of channel 4 of VCDAU and group 2 of the
coupled CDAU
QSUM1-3
Total reactive power group 1 of the coupled CDAU
QSUM5-7
Total reactive power of VCDAU and group 2 of the coupled
CDAU
Q4
Reactive power of channel 4 group 1 of the coupled CDAU
Q8
Reactive power of channel 4 of VCDAU and group 2 of the
coupled CDAU
FREQ1
Frequency calculated using the best signal of the first
measured value recording group (channels 1 to 4) of the DAU
FREQ2
Frequency calculated using the best signal of the second
measured value recording group (channels 5 to 8) of the DAU
Total powers are calculated from the first 3 channels of a group.
VDAU and not coupled CDAU
FREQ1
Frequency calculated using the best signal of the first
measured value recording group (channels 1 to 4) of the DAU
FREQ2
Frequency calculated using the best signal of the second
measured value recording group (channels 5 to 8) of the DAU
Select one calculated values from the drop-down menu of the
Channel
box.
Enter the
Channel Description
and
Abbreviation
and select a
Color
.
Select under
Display in
OSCOP P
whether the values of the channel are to be displayed in
the OSCOP P Evaluate module.
Use the
Display range min
and
Display range max
boxes to set the lowest or highest
respectively measured value to be displayed in the OSCOP P Evaluate module. Select the
measured value dimension.
Set the value for the zero crossing in the
Time axis position
box for evaluating the measured
values in the OSCOP P Evaluate module. Negative values are allowed.
Note
Digits following the points are regarded as decimal places.
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...