12
12.11 Slot Description
155
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
12.11.2 Analog Channels
The
Analog Channels
tab is provided for VCDAU, VDAU and CDAU modules.
Figure 12-22 Analog Channels tab
You can parameterize the following channels depending on the DAU type:
Select one of the 8 channels from the drop-down menu of the
Channel
box.
Change the
Channel Description
and
Abbreviation
and select a
Color
(if necessary).
Select with
Matching Transducer Core
the input voltage range for the VCDAU or VDAU.
Select the input voltage range for the VDAU or VCDAU under
Primary Operating Voltage
.
Enter the nominal voltage as phase-to-phase voltage and select the primary dimension of the
measured values (e. g. kV).
Enter the transformation ratio of the transducer in the
Primary VT nominal value
and
Secondary VT nominal value
and select the appropriate primary-side dimension of the
measured value unit from the drop-down menu.
The following reference values are valid for the connection of the measuring signals:
Star
Phase-to-ground
values
Delta
Phase-to-phase
values
Monophase/1-phase
Phase
values
3-phase
Phase
currents
VCDAU
Voltages V1 to V4 and currents I1 to I4
VDAU
Voltages V1 to V8
CDAU
Currents I1 to I8
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...