3 System Messages
280
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
A.3
System Messages
The table below contains all messages that the SIMEAS R-PMU logs in the log file:
Legend:
Type 0: Malfunction
Type 1: Warning / important message
Type 2: Operating message
Log No.
Type
Class
Description
Comment
258
1
BOOT
Reboot initiated
-
260
0
BOOT
Fault: Task monitor initiating reboot
Hotline
262
1
SYSTEM
Create system data OK
Reorganization of system internal data,
e. g. after upgrade or update
263
0
SYSTEM
Create system data canceled with fault
Hotline
265
1
SYSTEM
Read system data OK
-
266
1
SYSTEM
System data missing or wrong, new file
written
Reorganization of system internal data,
e. g. after upgrade
267
1
SYSTEM
Write system data OK
-
268
1
SYSTEM
Shutdown measurement system
Possible reasons: Change to service mode,
DAU error or device is being shut down
269
0
SYSTEM
Restart due to critical system fault
(deadlock). Fault time:
Hotline
270
0
SYSTEM
Restart due to critical system fault
(deadlock). Task:
Hotline
273
1
SYSTEM
DAU not plugged
Status message
274
0
SYSTEM
DAU boot fault
Several possible reasons: DAU and CPU
software version do not match, firmware
update recommended; DAU hardware error;
contact hotline if necessary
277
2
SYSTEM
Self-monitoring
-
278
0
SYSTEM
Fault: Cannot start self-monitoring
Hotline
279
2
SYSTEM
Self-monitoring: New MD5 checksum file
created
Checksum file is created again after each
firmware update
280
0
SYSTEM
Self-monitoring fault: Cannot write MD5
checksum file
Hotline
281
0
SYSTEM
Self-monitoring fault: Critical checksum fault Flash disk fault; Hotline
282
1
SYSTEM
Firmware update
-
283
0
SYSTEM
Firmware update failed
Hotline
284
1
SYSTEM
Communication subsystem not started.
Reason:
Hotline
285
1
SYSTEM
Measurement system not started. Reason:
Possibly an error message after an
upgrade, otherwise firmware or OSCOP P
update recommended; contact hotline if
necessary
286
1
SYSTEM
Number of device restarts due to critical
system faults:
For further information on this fault, refer to
detailed log entries.
287
0
SYSTEM
Fault writing the restart counter
Hotline
288
0
SYSTEM
Last restart due to critical system fault
Hotline
289
2
SYSTEM
Restart information written
-
290
2
SYSTEM
Fault writing the restart information
Hotline
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...