6
6.2 Measured Values and Calculation Values
46
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
6.2
Measured Values and Calculation Values
Table 6-3
SIMEAS R-PMU measured values
Measured value
Calculation Value
Four-phase connection
Three-phase
connection
Monophase
Voltage
V
L1
, V
L2
, V
L3
, V
N
V
L12
,
V
L23
,
V
L31
,
V
4
V
L12
, V
L23
, V
L31
, V
4
V
L1
, V
L2
, V
L3
, V
L4
Current
I
L1
, I
L2
, I
L3
, I
N
I
L1
, I
L2
, I
L3
,
I
4
I
L1
, I
L2
, I
L3
, I
L4
Voltage (vectorial)
V
L1
, V
L2
, V
L3
, V
N
V
L12
, V
L23
, V
L31
, V
4
V
L12
, V
L23
, V
L31
,
V
4
V
L1
, V
L2
, V
L3
, V
L4
Current (vectorial)
I
L1
, I
L2,
I
L3
, I
N
I
L1
, I
L2
, I
L3
, I
4
I
L1
, I
L2
, I
L3
, I
L4
Voltage (average)
V
L1
, V
L2
, V
L3
, V
N
V
L12
, V
L23
, V
L31
, V
4
V
L12
, V
L23
, V
L31
,
V
4
V
L1
, V
L2
, V
L3
, V
L4
Current (average)
I
L1
, I
L2
, I
L3
, I
N
I
L1
, I
L2
, I
L3
, I
4
I
L1
, I
L2
, I
L3
, I
L4
Positive-sequence system
V
1
, I
1
,
ϕ
1
V
1
, I
1
,
ϕ
1
–
Negative-sequence system V
2
, I
2
,
ϕ
2
V
2
, I
2
,
ϕ
2
–
Zero-sequence system
V
0
, I
0
,
ϕ
0
–
–
Frequency
f
f
f
Phase angle
ϕ
ϕ
ϕ
Active power
P
P
P
Reactive power
Q
Q
Q
Binary signals
B
B
B
Process signals
D
D
D
Note
With a three-phase connection, the powers are measured using the two-wattmeter method (Aron
circuit).
Note
DDAUs record process signals. The values to be measured must be adjusted to the signal levels
of the signal to be measured.
Example: Process signals (e. g., -50 °C to +100 °C) can be assigned to a physical input range
(e. g., DC -10 V to DC +10 V). It is also possible to define the neutral point.
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...