18
18.1 Modules of the SIMEAS R-PMU
263
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Communication interfaces
Recommended for SIMEAS R-PMU: 192.168.subnet.device (subnet: 1 to 254
and device: 1 to 254)
Supply voltage
Normal operation
Emergency operation with battery package:
Table 18-1
LAN: Ethernet class C
(recommended)
Class
Range of network numbers
Subnet mask
C
192.0.0.x to 223.255.255.x
255.255.255.0
Table 18-2
COM 1 setting
Setting
Baud rate
9,600 bit/s to 115,200 bit/s
Data bits
8
Stop bits
1
Parity
none
Table 18-3
COM S setting
Setting
Baud rate
19,200 bit/s
Data bits
8
Stop bits
1
Parity
none
Table 18-4
Supply voltages
Voltage type
Rated voltages
Permissible range
DC (low-voltage)
DC 24 V / DC 48 V / DC 60 V
DC 19.2 V to DC 72 V
DC (high-voltage)
DC 110 V / DC 125 V / DC 220 V /
DC 250 V
DC 88 V to DC 300 V
AC (50 Hz / 60 Hz)
AC 115 V / AC 230 V
AC 92 V to AC 276 V;
45 Hz to 65 Hz
Table 18-5
Battery package (NiCd)
Values
Rated direct voltage
DC 12 V
Rated capacity
1.2 Ah
Duration of emergency power operation
at least 10 min
Useful power reserve
12 Wh
Temperature range
-20 °C to +70 °C
Service life
3 years (at an ambient temperature of 55 °C)
Содержание SIMEAS R-PMU
Страница 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 40: ...5 5 4 Monophase Connection 40 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 210: ...14 14 4 Commissioning 210 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 274: ...18 18 4 Time Synchronization 274 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 290: ...5 Special Note Open Source Software 290 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 292: ...Literature 292 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Страница 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...