Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
TIM DNP3
296
System Manual, 12/2015, C79000-G8976-C253-04
Event ID
(hex)
Detailed
event
(hex)
Status message
Meaning / remark
F460
0808
Message queue overflow (outgoing)
Meaning in byte 5 of the diagnostics message:
•
1 = LAN COM
•
2 = S7 adapter
•
3 = Modbus adapter
F960
0809
CTS error (incoming)
F860
0809
CTS error (outgoing)
F560
080A
UART error (incoming)
F460
080A
UART error (outgoing)
F360
080B
Status change of the MODBUS slave
(incoming)
MODBUS slave not accessible
F260
080B
Status change of the MODBUS slave
(outgoing)
MODBUS slave accessible
F560
080C
Negative S7 acknowledgement re-
ceived (message only incoming)
Byte 6 of the message codes the error class (ERRCLS)
and byte 7 codes the error code (ERRCOD). For the
meaning of ERRCLS and ERRCOD, see Meaning of
F560
080D
Negative S7 access result received
(message only incoming)
Bytes 6 and 7 of the message code the access result
(hex) with the following meaning:
•
FF = success
•
01 = hardware error
•
02 = temporary lack of resources
•
03 = object access not permitted
•
05 = invalid address
•
06 = type not supported
•
07 = type inconsistent
•
0A = object does not exist
•
0E...EF: Reserved
•
FE = data unchanged since last access
7.3.6.5
Meaning of ERRCLS and ERRCOD
Meaning of ERRCLS and ERRCOD in messages 0113 and 080C
Table 7- 6
Meaning of ERRCLS and ERRCOD (hex)
ERRCLS
ERRCOD Meaning
FF
01
The LAN connection via which the frame is to be sent is not established. The message is
deleted.
FF
02
The queue of the LAN connection via which the frame is to be sent has overflowed. The mes-
sage is deleted.
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...